Products Relays
T-PRO 4000 Transformer Protection & Monitoring Relay
The IEC 61850 station bus embedded T-PRO 4000 relay provides complete transformer fault and overload protection, DFR-quality fault oscillography, sequence of event logging, trend recording, transformer monitoring and overload early warning (TOEWS) in a fully integrated protective relay solution.
Protection
- 5 sets of CT inputs for differential protection
- Software control compensates current magnitude and angle
- Protection functions include IEEE devices 87, 87N, 49, 67, 50/51, 50N/51N, 24INV/DEF, 59N, 60, 81, THD, 27, Temperature Control and TOEWS©
- ProLogic - 10 control logic statements
- Asset management to maximize use of transformer capacity (ANSI/IEEE C57.91-1995)
Recording, Monitoring and Metering
- High quality recording - fault recording (96 samples/cycle), 30 to 600 day load trending and event logging (1 ms)
- Adaptive overload - auto-adjust overload characteristics based on temperature
- Controlled load management
- Transformer Overload Early Warning System (TOEWS©) with predictive 15 and 30 minute alarms
- Through fault monitoring
Substation Automation - Ethernet Ready
- IEC 61850 Station Bus on dedicated Optical/Copper Ethernet Ports
- Enhanced DNP3 SCADA communication protocol including point lists, class support and multiple master station support
- Modbus SCADA communication protocol
- IRIG-B port (through BNC connector) for precise time stamping and sample synchronization
- Serial communication port
- 30 virtual inputs for local and remote control
- Optional internal modem
Easy to Use
- Easy to use, simplified relay setting and record analysis software (Windows® 2000/XP) included
- Intuitive ASCII-terminal interface provides full local or remote access
|